Skip to main content
Network Thinking Solutions Logo

CVE-2025-3756

A vulnerability exists in the command handling of the IEC 61850 communication stack included in the product revisions listed as affected in this CVE. An attacker with access to IEC 61850 networks could exploit the vulnera bility by using a specially…

All CVEs
CVE-2025-3756Published 4/13/2026

A vulnerability exists in the command handling of the IEC 61850 communication stack included in the product revisions listed as affected in this CVE. An attacker with access to IEC 61850 networks could exploit the vulnera bility by using a specially…

Vendor advisory
CVSS7.1High

Overview

A vulnerability exists in the command handling of the IEC 61850 communication stack included in the product revisions listed as affected in this CVE. An attacker with access to IEC 61850 networks could exploit the vulnera bility by using a specially crafted 61850 packet, forcing the communication interfaces of the PM 877, CI850 and CI868 modules into fault mode or causing unavailability of the S+ Operations 61850 connectivity, resulting in a denial-of-service situation.  The System 800xA IEC61850 Connect is not affected. Note: This vulnerability does not impact on the overall availability and functionality of the S+ Operations node, only the 61850 communication function.     This issue affects AC800M (System 800xA): from 6.0.0x through 6.0.0303.0, from 6.1.0x through 6.1.0031.0, from 6.1.1x through 6.1.1004.0, from 6.1.1x through 6.1.1202.0, from 6.2.0x through 6.2.0006.0; Symphony Plus SD Series: A_0, A_1, A_2.003, A_3.005, A_4.001, B_0.005; Symphony Plus MR (Melody Rack): from 3.10 through 3.52; S+ Operations: 2.1, 2.2, 2.3, 3.3.

Published
4/13/2026
Last modified
10/14/2026
Assigned by
Not available
NVD analysis
Not available

Exploitation

No CISA KEV flag in the saved record

An absent KEV flag does not establish that exploitation has never occurred. Verify current intelligence before prioritizing work.

EPSS predictions and CISA SSVC assessments are not imported here. Review additional intelligence on Cloudflare

Affected products

Affected-version rules published in the advisory. Conditions and uncertain comparisons require verification.

Vendor / productAffected versionsPlatform / conditionsEvidence
AC800M (System 800xA)
ABB
≥ 6.0.0x, ≤ 6.0.0303.0

Verify advisory

Source
AC800M (System 800xA)
ABB
≥ 6.1.0x, ≤ 6.1.0031.0

Verify advisory

Source
AC800M (System 800xA)
ABB
≥ 6.1.1x, ≤ 6.1.1004.0

Verify advisory

Source
AC800M (System 800xA)
ABB
≥ 6.1.1x, ≤ 6.1.1202.0

Verify advisory

Source
AC800M (System 800xA)
ABB
≥ 6.2.0x, ≤ 6.2.0006.0

Verify advisory

Source
Symphony Plus SD Series
ABB
A_0

Verify advisory

Source
Symphony Plus SD Series
ABB
A_1

Verify advisory

Source
Symphony Plus SD Series
ABB
A_2.003

Verify advisory

Source
Symphony Plus SD Series
ABB
A_3.005

Verify advisory

Source
Symphony Plus SD Series
ABB
A_4.001

Verify advisory

Source
Symphony Plus SD Series
ABB
B_0.005

Verify advisory

Source
Symphony Plus MR (Melody Rack)
ABB
≥ 3.10, ≤ 3.52

Verify advisory

Source
S+ Operations
ABB
2.1

Verify advisory

Source
S+ Operations
ABB
2.2

Verify advisory

Source
S+ Operations
ABB
2.3

Verify advisory

Source
S+ Operations
ABB
3.3

Verify advisory

Source

Recommended actions

Verify the product, installed version, platform, and advisory prerequisites on each system. Apply the vendor's applicable fixed release or mitigation. An affected-range boundary alone is not a universal update recommendation.

Vendor advisory links

Derived from non-aggregator references because the source record has no vendor tags. Verify the advisory before acting on it.

Severity

CVSS describes technical impact. It is separate from exploitation evidence.

Published headline score: 7.1. Score version, vector, and attribution are not available in this record. Additional score details appear when the source record is next refreshed.

Sources & references

Sources: Official CVE List, NVD and cve.now (summaries CC BY 4.0). Uses NVD data; not endorsed by NVD.